3 Phase Electric Inverter Pure Sine With 10KVA -120KVA 110VDC
Product Details:
Place of Origin: | Shenzhen China |
Brand Name: | HRD/OEM |
Certification: | CE, ISO9001:2008 |
Model Number: | EF3310, EF3320,,, EF33120 |
Payment & Shipping Terms:
Minimum Order Quantity: | 2 |
---|---|
Price: | 3100USD |
Packaging Details: | Wooden case with pallet |
Delivery Time: | 3 weeks after down payment |
Payment Terms: | TT |
Supply Ability: | 500nos/ month |
warranty: | 2years after shipment |
Detail Information |
|||
Product Name: | Electricity Inverter | IP Grade: | 20 |
---|---|---|---|
Transfer Time: | 0ms (Inverter To Bypass,bypass To Inverter) | Cooling: | Forced Cooling |
Wave Form: | Pure Sine Wave | Phase: | 3PHASE +N+G |
Highlight: | electricity inverter,sine wave inverter |
Product Description
Introduction: EF series 3phase industrial power inverter is adopted with advanced technology and high-frequency pulse width modulation control of the CPU design of new inverter technology, super high reliability, protection-function, small waveform distortion, etc..
It can be converted to 110V AC or 220Vac 50/60Hz, voltage, frequency stability, with pure sine wave AC power. The product has a high conversion efficiency. (up to 85%@ 100% load). As well as a strong non-linear load drive capability. The input voltage, current and output voltage and current monitoring for detection, in order to achie ve maintenance-free guarded function.
Application: Power plant, transformer substation, electricity system, rail system, oil, gas, harsh environment etc.
Main Features:
- Fully advanced DSP technology
- 7inch large colorful touch screen with high resolution
- Inverter Priority
- With AC bypass function
- Manual bypass fail-safe design to avoid wrong operation
- Output and battery insulated completely
- Full protection,input low,high voltage, output overload, short circuit
- Intelligent Large LCD display and easy maintenance
- Smart RS232(SNMP CARD option), Dry contact;
- Stable Parallel technology(N+1), common battery;
- Event log function,1000events;
Model |
EF3310 |
EF3315 |
EF3320 |
EF3330 |
EF3340 |
EF3360 |
EF3380 |
EF33100 |
EF33120 |
|
Capacity |
10KVA |
15KVA |
20KVA |
30KVA |
40kva |
60KVA |
80KVA |
100KVA |
120kva |
|
Input |
||||||||||
Phase |
3PHASE +N+G |
|||||||||
Bypass range |
380/400v+/-15% |
|||||||||
DC |
110Vdc/220Vdc ± 20% |
220Vdc ± 20% |
||||||||
voltage |
220/230Vac+/-15%(AC mode);220/230Vac +/-1% 1Ph 50Hz (INV. mode) |
|||||||||
output |
||||||||||
P.F |
0.8 |
|||||||||
Wave form |
Pure sine wave |
|||||||||
THDi |
< 2% |
|||||||||
Over load |
105%~125%10mins;125%~150%1min. |
|||||||||
Transfer time |
0ms (Inverter to bypass,bypass to inverter) |
|||||||||
display |
AC input voltage,frequency;DCinput voltage ,current; output voltage, frequency current, load etc. |
|||||||||
alarm |
DC input high or low,inverter failure,unsynchronization,bypass failure,bypass output,overload |
|||||||||
Environment |
||||||||||
Cooling |
Forced cooling |
|||||||||
Temp. |
0-40degree |
|||||||||
Humidity |
0%-90%(non-condensing) |
|||||||||
Noise |
52-58Db(1m) |
|||||||||
Physical |
||||||||||
IP grade |
20 |
|||||||||
Unit Size(L*W*H) |
600*600*1280(mm) |
800×800×1600mm |
800×800×1800mm |
|||||||
Weight(kg) |
230 |
250 |
260 |
305 |
345 |
500 |
560 |
610 |